Motor control centre · MCC
MCC panels
One lineup that starts, stops and protects the motors in your plant. An MCC groups motor starter feeders on a common busbar, with local and remote control, status indication and interfaces to your PLC or SCADA.
- Busbar rating
- Up to 4000 A
- Fault level
- Up to 50 kA, 1 s
- Starters
- DOL, SD, soft, VFD
- Modules
- Fixed or drawout
Overview
We design each MCC around your motor list. Every feeder is sized for its motor's kW rating and starting method, with Type 2 coordination between the breaker, contactor and overload relay so a fault on one motor doesn't damage the starter.
Modules can be fixed, plug-in or fully drawout. Drawout MCCs let you pull out a faulty starter and replace it with a spare in minutes without shutting down the rest of the board, which matters on process lines that can't stop.
Technical specifications
| Rated operational voltage | 415 V AC, 3-phase 4-wire, 50 Hz |
|---|---|
| Control voltage | 230 V AC or 24/110 V DC |
| Main busbar current | Up to 4000 A |
| Short-time withstand current | Up to 50 kA for 1 s |
| Incomer | ACB or MCCB, with metering and protection |
| Starter types | DOL, star-delta, soft starter and VFD feeders |
| Coordination | Type 2 between MCCB/MPCB, contactor and overload relay |
| Module construction | Fixed, plug-in or drawout with service, test and isolated positions |
| Motor protection | Thermal or electronic overload relays; motor protection relays on large drives |
| Control and indication | Local/remote selector, start/stop push buttons, run/trip/off lamps, ammeter per feeder |
| Form of separation | Form 3b or Form 4b |
| Enclosure | CRCA sheet steel, 2 mm structure and 1.6 mm doors and covers |
| Degree of protection | IP42 or IP54, indoor |
| Finish | Powder coat, RAL 7035 or your shade |
| Standards | IS 8623; starters to IEC 60947-4-1 |
What's inside
- ACB or MCCB incomer with metering
- Horizontal main busbar and vertical droppers to each module
- Starter modules with MCCB or MPCB, contactors and overload relays
- Soft starter and VFD sections with forced ventilation
- Control terminals and interposing relays for PLC/SCADA
- Spare modules and space for future feeders
Applications
- Pumping stations and water treatment
- Cement, steel and chemical plants
- Food, pharma and packaging lines
- HVAC plant rooms and chillers
- Conveyors and material handling
- Compressor houses
Options
- Intelligent MCC with Modbus/Profibus feeders
- Motor protection relays with thermal models
- Harmonic filters and line reactors for VFDs
- Remote I/O and hard-wired PLC interface
- Space heaters and anti-condensation
- Spare drawout modules
Built and tested in-house
We cut, bend, weld and powder-coat the enclosures in our own workshop, then assemble and wire every panel to drawings you approve before fabrication starts. Before dispatch each panel goes through high-voltage, insulation resistance and functional tests, and your team is welcome to witness them.
Frequently asked questions
When should I choose a drawout MCC over a fixed one?
Choose drawout when downtime is expensive. A faulty module can be withdrawn and a spare plugged in without switching off the rest of the MCC. Fixed MCCs cost less and suit plants where planned shutdowns are acceptable.
What is Type 2 coordination?
Under IEC 60947-4-1, Type 2 coordination means that after a short circuit the starter is still fit for further use, apart from possible light welding of contactor contacts. It limits damage and repair time on each feeder.
Can VFDs and soft starters go in the same MCC?
Yes. We place drives in dedicated sections with ventilation sized for their losses, and add line reactors or filters where harmonics need to be controlled.
Do you wire the MCC to our PLC?
We bring start, stop, run, trip and remote/local signals to terminals marked for your PLC, or provide communication-enabled feeders on Modbus or Profibus.